3 Phase kWhmeter via CT 1A or 5A 4M S0 MID ECP300C

EAN-Nr.
3250612231393
Packaging
1 Prt.

Technical characteristics

Architecture
  • Number of poles
    4 P
Functions
  • Precision class
    B
  • Tarif type
    T1...T2 (230 V AC) / -
Configuration
  • Number of modules
    4
Compatibility
  • Suitable for
    Purchase / supply
Main electrical features
  • Rated operational voltage Ue
    92 / 480 V
  • Type of supply voltage
    AC
  • Frequency
    50 Hz
Voltage
  • Max operating voltage
    300 V
  • Rated impulse withstand voltage
    6 kV
Electric current
  • Minimum operating current
    0.001 A
  • Operating current
    0.001 / 6 A
  • Rated current
    5 A
  • Reference current
    1 A
  • Max. measurement circuit current
    6 A
Dimensions
  • Depth of installed product
    60 mm
  • Height of installed product
    90 mm
  • Width of installed product
    72 mm
Power
  • Power consumed
    2 VA
  • Total power loss under IN
    0.6 W
  • Plage Impulsion/KWh
    1 / 10000 Imp/kWh
Electrical specifications
  • Type of pulse generator
    électrical
Measurement
  • Frequency measuring range
    45 to 65 Hz
  • Type of measuring instrument
    electronical
  • Principle of measurement
    Measurement transformer
Installation, mounting
  • Tightening torque
    0.5Nm
Settings
  • Value of a pulse
    100 Wh
  • Transformer interpretation adjustable
    1
Equipment
  • Type of display
    retro illuminated display
  • Tariff model of kilowatt-hour meter
    Externa
  • Type of counter
    three-phase counter with torus of measurement and impulses output
Use
  • Pulse duration
    30 / 100 ms
  • Transformation Ratio
    50;5 ; 100;5 ; 200;5 ; 250;5 ; 300;5 ; 400;5 ; 600;5 ; 800;5 ; 1000;5 ; 1250;5 ; 1500;5
Standards
  • Standard text
    EN 50470-1 / 3 ; IEC 62053-21 / 23 ; IEC 61557-12
  • Certified product
    MID (Measuring Instruments Directive)
Safety
  • Protection index IP
    IP20
  • Protection class
    isol.class II
  • Halogen free
    No
Use conditions
  • Operating temperature
    -25…55 °C
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    2
  • Altitude
    2000 m
  • Storage/transport temperature
    -25…70 °C