Moulded Case Circuit Breaker h3+ P160 TM ADJ 3P3D 63A 25kA CTC HHS063DC

EAN-Nr.
3250613177942
Packaging
1 Prt.

Technical characteristics

Architecture
  • Neutral position
    without neutral
  • Number of protected poles
    3
  • Number of poles
    3 P
  • Type of case
    Fixed built-in
Functions
  • Complete device with protection unit
    Yes
  • Reversing switch
    No
  • Version as main switch
    Yes
  • Version as emergency stop installation
    No
  • Version as safety switch
    No
  • Version as maintenance-/service switch
    Yes
  • Trip Unit
    TM A/A
  • Integrated earth fault protection
    No
Controls and indicators
  • Motor drive integrated
    No
Main electrical features
  • Rated operational voltage Ue
    220 / 690 V
  • Type of supply voltage
    AC
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    800 V
  • Rated impulse withstand voltage
    8 kV
  • With under voltage release
    No
Electric current
  • Rated current
    63 A
  • Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2
    6 kA
  • Thermal protection nob setting xIN
    0.63 / 0.8 / 1
  • Rating current 10°C according to IEC 60947
    87.1 A
  • Rating current 15°C according to IEC 60947
    84.5 A
  • Rating current 20°C according to IEC 60947
    81.7 A
  • Rating current 25°C according to IEC 60947
    78.9 A
  • Rating current 30°C according to IEC 60947
    76 A
  • Rating current 35°C according to IEC 60947
    73 A
  • Rating current 40°C according to IEC 60947
    69.8 A
  • Rating current 45°C according to IEC 60947
    66.5 A
  • Rating current 50°C according to IEC 60947
    63 A
  • Rating current 55°C according to IEC 60947
    59.3 A
  • Rating current 60°C according to IEC 60947
    55.4 A
  • Rating current 65°C according to IEC 60947
    51.1 A
  • Rating current 70°C according to IEC 60947
    46.5 A
  • Rated service breaking capacity Ics under 660V AC according IEC 60947-2
    6 kA
  • Breaking capacity on 1 pole for IT 230V NF 60947-2
    6 kA
  • Breaking capacity on 1 pole for IT 400V NF 60947-2
    6 kA
  • Breaking capacity on 1 pole for IT 415V NF 60947-2
    6 kA
  • Breaking capacity on 1 pole for IT 690V NF 60947-2
    2.5 kA
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    35 kA
  • Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
    35 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    25 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    25 kA
  • Range of the thermal adjustment
    40 / 50 / 63 A
  • Rated service breaking capacity Ics under 110-138V AC according IEC 60947-2
    35 kA
  • Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2
    35 kA
  • Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
    25 kA
  • Rated ultimate short-circuit breaking capacity Icu under 660V AC IEC 60947-2
    6 kA
Dimensions
  • Depth of installed product
    97 mm
  • Height of installed product
    130 mm
  • Width of installed product
    90 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Power loss per pole at 0.63*In
    1.43 W
  • Power loss per pole at 0.8*In
    2.24 W
  • Total power loss at 0.63*In
    4.3 W
  • Total power loss at 0.8*In
    6.72 W
  • Total power loss under IN
    10.5 W
  • Power loss per pole at In
    3.5 W
Tripping
  • Short-time delayed tripping
    No
Endurance
  • Electric endurance in number of cycles
    10000
  • Number of mechanical operations
    40000
Cover, door
  • Interlockable
    Yes
Installation, mounting
  • Tightening torque
    6Nm
  • DIN rail mounting with optional adaptator
    Yes
  • Suitable for front mounting center
    No
  • Suitable for front mounting
    No
  • Suitable for ground mounting
    Yes
Connection
  • Type of connection
    with screw
Protection
  • Instantaneous protection (Ii): type
    fixed
Cable
  • Cable Material
    Cu
Settings
  • Range of the magnetic adjustment
    378 / 504 / 630 / 756 A
  • Magnetic protection nob setting xIN
    6 / 8 / 10 / 12
Equipment
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as normally open contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Motor drive optional
    No
  • Can be accessorized
    Yes
Use cases
  • Category of use
    A
Use
  • Vibrations and shocks withstand
    IEC 68068-2-52 Test FC
Standards
  • Standard text
    IEC 60947-2
Safety
  • REACH conform
    Yes
  • RoHS conform
    Yes
  • Halogen free
    No
Use conditions
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    3
  • Altitude
    2000 m
  • Air humidity protection
    95%HR 55°C sev Kn (IEC 68-2-30/52)
temperatur
  • Temperature of calibration
    50 °C