Technical characteristics

Architecture
  • Neutral position
    without neutral
  • Number of protected poles
    3
  • Number of poles
    3 P
  • Type of case
    Fixed built-in
Functions
  • Complete device with protection unit
    Yes
  • Trip Unit
    TM F/F
  • Integrated earth fault protection
    No
  • Concurrently switching N-neutral
    No
Controls and indicators
  • Motor drive integrated
    No
Main electrical features
  • Rated operational voltage Ue
    220 / 415 V
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    690 V
  • Rated impulse withstand voltage
    8 kV
  • With under voltage release
    No
Electric current
  • Rated current
    50 A
  • Thermal protection nob setting xIN
    1
  • Rating current 10°C according to IEC 60947
    60.4 A
  • Rating current 15°C according to IEC 60947
    59.2 A
  • Rating current 20°C according to IEC 60947
    58 A
  • Rating current 25°C according to IEC 60947
    56.7 A
  • Rating current 30°C according to IEC 60947
    55.4 A
  • Rating current 35°C according to IEC 60947
    54.1 A
  • Rating current 40°C according to IEC 60947
    52.8 A
  • Rating current 45°C according to IEC 60947
    51.4 A
  • Rating current 50°C according to IEC 60947
    50 A
  • Rating current 55°C according to IEC 60947
    48.5 A
  • Rating current 60°C according to IEC 60947
    47 A
  • Rating current 65°C according to IEC 60947
    45.4 A
  • Rating current 70°C according to IEC 60947
    43.8 A
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    40 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    40 kA
  • Range of the thermal adjustment
    50 A
  • Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
    40 kA
Dimensions
  • Depth of installed product
    68 mm
  • Height of installed product
    130 mm
  • Width of installed product
    75 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Total power loss under IN
    17.3 W
  • Power loss per pole at In
    5.8 W
Endurance
  • Electric endurance in number of cycles
    1000
  • Number of mechanical operations
    4000
Installation, mounting
  • DIN rail mounting with optional adaptator
    No
Connection
  • Type of connection
    with screw
Settings
  • Range of the magnetic adjustment
    600 A
Equipment
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as normally open contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Motor drive optional
    No
  • Can be accessorized
    Yes
Standards
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP4X
Use conditions
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    3
  • Altitude
    2000 m
temperatur
  • Temperature of calibration
    50 °C

Downloads

  • Product image

    Image HNA050Z  | Hager

    Product Image HNA050Z

  • Product notice

    Image Instruction manuals for HNA050Z  | Hager

    Instruction manuals for HNA050Z

    PDF
    8 MB
  • Product declaration

    Image EU Declaration of conformity for HNA050Z  | Hager

    EU Declaration of conformity for HNA050Z

    Declaration

    PDF
    215 KB
  • Product ROHS

    Image RoHS certificate for HNA050Z  | Hager

    RoHS certificate for HNA050Z

    PDF
    33 KB
    Image RoHS certificate for HNA050Z  | Hager

    RoHS certificate for HNA050Z

    PDF
    32 KB
More documentation