HNA063U

HNA063U MCCB X160 3P 40kA 63A

HNA063U

MCCB X160 3P 40kA 63A

Cat ref.:HNA063U
prt.
EAN No.:

3250613130541

P.U.:1 prt.
Technical Characteristics
Type of order:Toggle
Type of case:Fixed built-in
Number of poles:3 P
Type of pole:3P3D
Complete device with protection unit:yes
Trip Unit:TM A/F
Integrated earth fault protection:no
Motor drive integrated:no
Rated operational voltage Ue:220/415 V
Frequency:50/60 Hz
Rated insulation voltage:690 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:40 kA
Rated service breaking capacity Ics AC according IEC 60947-2:50 %
Breaking capacity on 1 pole with 230 V NF 60947-2:51 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:40 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:6 kA
Thermal protection nob setting xIN:0,63/0,8/1
Rating current 10°C according to IEC 60947-2:71,7 A
Rating current 150°C according to IEC 60947-2:70,7 A
Rating current 20°C according to IEC 60947-2:69,6 A
Rating current 25°C according to IEC 60947-2:68,6 A
Rating current 30°C according to IEC 60947-2:67,5 A
Rating current 35°C according to IEC 60947-2:66,4 A
Rating current 40°C according to IEC 60947-2:65,3 A
Rating current 45°C according to IEC 60947-2:64,1 A
Rating current 50°C according to IEC 60947-2:63 A
Rating current 55°C according to IEC 60947-2:61,8 A
Rating current 60°C according to IEC 60947-2:60,6 A
Rating current 65°C according to IEC 60947-2:59,3 A
Rating current 70°C according to IEC 60947-2:58,1 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power loss per pole at 0.63*In:4 W
Power loss per pole at 0.8*In:6,3 W
Total power loss at 0.63*In:12,1 W
Total power loss at 0.8*In:18,9 W
Total power loss under IN:30 W
Power loss per pole at In:10 W
Tripmode:TM
time of response when opening:10 ms
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Tightening torque:6Nm
DIN rail mounting with optional adaptator:yes
Connection cross-sect. flexible cable:4 / 70mm²
Connection cross-sect. rigid cable:4 / 95mm²
Connection:Front connection
type of connection:with screw
Range of the magnetic adjustment:1000 A
Motor drive optional:no
Category of use:A
Standard text:IEC 60 947-2
European directive RoHs:voluntary compliance
European directive WEEE:not concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates
  • HNA063U
    HNA063U MCCB X160 3P 40kA 63A
    HNA063U
  • HNA063U MCCB X160 3P 40kA 63A
Data is subject to errors and technical modifications.