HNB250Z

HNB250Z MCCB x250 3P 40kA 250A TM

HNB250Z

MCCB x250 3P 40kA 250A TM

Cat ref.:HNB250Z
prt.
EAN No.:

3250613149949

P.U.:1 prt.
Technical Characteristics
Type of order:Toggle
Type of case:Fixed built-in
Number of poles:3 P
Type of pole:3P3D
Complete device with protection unit:yes
Trip Unit:TM F/F
Integrated earth fault protection:no
Motor drive integrated:no
Rated operational voltage Ue:220/415 V
Frequency:50/60 Hz
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:40 kA
Rated service breaking capacity Ics AC according IEC 60947-2:50 %
Breaking capacity on 1 pole with 230 V NF 60947-2:51 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:40 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:4 kA
Thermal protection nob setting xIN:1
Rating current 10°C according to IEC 60947-2:299 A
Rating current 150°C according to IEC 60947-2:293,2 A
Rating current 20°C according to IEC 60947-2:287,5 A
Rating current 25°C according to IEC 60947-2:281,7 A
Rating current 30°C according to IEC 60947-2:275,5 A
Rating current 35°C according to IEC 60947-2:269,5 A
Rating current 40°C according to IEC 60947-2:263 A
Rating current 45°C according to IEC 60947-2:256,5 A
Rating current 50°C according to IEC 60947-2:250 A
Rating current 55°C according to IEC 60947-2:243 A
Rating current 60°C according to IEC 60947-2:236,2 A
Rating current 65°C according to IEC 60947-2:229,2 A
Rating current 70°C according to IEC 60947-2:222,2 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Total power loss under IN:48 W
Power loss per pole at In:16 W
Tripmode:TM
time of response when opening:10 ms
Electric endurance in number of cycles:10000
Number of mechanical operations:20000
Tightening torque:12Nm
DIN rail mounting with optional adaptator:yes
Connection cross-sect. flexible cable:35 / 150mm²
Connection cross-sect. rigid cable:35 / 185mm²
Connection:Front connection
type of connection:Terminal
Range of the magnetic adjustment:2750 A
Magnetic protection nob setting xIN:10
Motor drive optional:yes
Category of use:A
Standard text:IEC 60 947-2
European directive RoHs:voluntary compliance
European directive WEEE:concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates