HNC250G h3 MCCB h250 3x250A Plug In 50kA

HNC250G

h3 MCCB h250 3x250A Plug In 50kA

Cat ref.:HNC250G
prt.
EAN No.:

3250613123185

P.U.:1 prt.
Technical Characteristics
Type of order:Toggle
Type of case:PLUG-IN
Number of poles:3 P
Type of pole:3P3D
Complete device with protection unit:yes
Trip Unit:LSI
Integrated earth fault protection:no
Motor drive integrated:no
Rated operational voltage Ue:220/690 V
Frequency:50/60 Hz
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:50 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:85 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:50 kA
Rating current 30°C according to IEC 60947-2:250 A
Rating current 40°C according to IEC 60947-2:225 A
Rating current 50°C according to IEC 60947-2:200 A
Rating current 55°C according to IEC 60947-2:200 A
Rating current 60°C according to IEC 60947-2:157,5 A
Rating current 65°C according to IEC 60947-2:157,5 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Tripmode:LSI
time of response when opening:10 ms
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Tightening torque:12Nm
DIN rail mounting with optional adaptator:yes
Connection cross-sect. flexible cable:35 / 150mm²
Connection cross-sect. rigid cable:35 / 185mm²
Connection:Front connection
type of connection:Terminal
Range of the magnetic adjustment:1400/1750/2240/2800/3150/3250/3250 A
Motor drive optional:yes
Category of use:A
Standard text:IEC 60 947-2
European directive WEEE:concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates