Moulded Case Circuit Breaker h3 x160 TM ADJ 3P3D 40A 18kA CTC HDA040U

EAN-Nr.
3250613130619
Packaging
1 Prt.

Technical characteristics

Architecture
  • Neutral position
    without neutral
  • Number of protected poles
    3
  • Number of poles
    3 P
  • Type of case
    Fixed built-in
Functions
  • Complete device with protection unit
    Yes
  • Trip Unit
    TM A/F
  • Integrated earth fault protection
    No
  • Concurrently switching N-neutral
    No
Controls and indicators
  • Motor drive integrated
    No
Main electrical features
  • Rated operational voltage Ue
    220 / 415 V
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    690 V
  • Rated impulse withstand voltage
    8 kV
  • With under voltage release
    No
Electric current
  • Rated current
    40 A
  • Thermal protection nob setting xIN
    0.63 / 0.8 / 1
  • Rating current 10°C according to IEC 60947
    49.8 A
  • Rating current 15°C according to IEC 60947
    48.7 A
  • Rating current 20°C according to IEC 60947
    47.5 A
  • Rating current 25°C according to IEC 60947
    46.4 A
  • Rating current 30°C according to IEC 60947
    45.2 A
  • Rating current 35°C according to IEC 60947
    43.9 A
  • Rating current 40°C according to IEC 60947
    42.6 A
  • Rating current 45°C according to IEC 60947
    41.3 A
  • Rating current 50°C according to IEC 60947
    40 A
  • Rating current 55°C according to IEC 60947
    38.5 A
  • Rating current 60°C according to IEC 60947
    37.1 A
  • Rating current 65°C according to IEC 60947
    35.6 A
  • Rating current 70°C according to IEC 60947
    34 A
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    25 kA
  • Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
    25 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    18 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    18 kA
  • Range of the thermal adjustment
    25 / 32 / 40 A
  • Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
    18 kA
Dimensions
  • Depth of installed product
    68 mm
  • Height of installed product
    130 mm
  • Width of installed product
    75 mm
Frequency
  • Frequency
    50 to 60 Hz
Power
  • Power loss per pole at 0.63*In
    1.4 W
  • Power loss per pole at 0.8*In
    2.3 W
  • Total power loss at 0.63*In
    4.3 W
  • Total power loss at 0.8*In
    7 W
  • Total power loss under IN
    11 W
  • Power loss per pole at In
    3.7 W
Endurance
  • Electric endurance in number of cycles
    1000
  • Number of mechanical operations
    4000
Installation, mounting
  • DIN rail mounting with optional adaptator
    No
Connection
  • Type of connection
    with screw
Settings
  • Range of the magnetic adjustment
    600 A
Equipment
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as normally open contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Motor drive optional
    No
  • Can be accessorized
    Yes
Standards
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP4X
Use conditions
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    3
  • Altitude
    2000 m
temperatur
  • Temperature of calibration
    50 °C

Downloads

  • Product image

    Image HDA040U  | Hager

    Product Image HDA040U

  • Product notice

    Image Instruction manuals for HDA040U  | Hager

    Instruction manuals for HDA040U

    PDF
    8 MB
  • Product declaration

    Image EU Declaration of conformity for HDA040U  | Hager

    EU Declaration of conformity for HDA040U

    Declaration

    PDF
    215 KB
  • Product ROHS

    Image RoHS certificate for HDA040U  | Hager

    RoHS certificate for HDA040U

    PDF
    33 KB
    Image RoHS certificate for HDA040U  | Hager

    RoHS certificate for HDA040U

    PDF
    32 KB
More documentation