HDA080U

No picture available

MCCB h3 x160 TM 3x80A 18kA

Cat ref.:HDA080U
prt.
EAN No.:

3250613130657

P.U.:1 prt.
Technical Characteristics
Number of protected poles:3
Number of poles:3 P
Type of pole:3P3D
Fixing mode:DIN rail type O or type J
Trip Unit:TM A/F
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Rated insulation voltage:690 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:18 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:18 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:18 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:18 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:18 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:18 kA
Thermal protection nob setting xIN:0,63/0,8/1
Range of the thermal adjustment:50/63/80 A
Rating current 10°C according to IEC 60947-2:93,2 A
Rating current 150°C according to IEC 60947-2:91,6 A
Rating current 20°C according to IEC 60947-2:90,1 A
Rating current 25°C according to IEC 60947-2:88,5 A
Rating current 30°C according to IEC 60947-2:86,8 A
Rating current 35°C according to IEC 60947-2:85,2 A
Rating current 40°C according to IEC 60947-2:83,5 A
Rating current 45°C according to IEC 60947-2:81,7 A
Rating current 50°C according to IEC 60947-2:80 A
Rating current 55°C according to IEC 60947-2:78,1 A
Rating current 60°C according to IEC 60947-2:76,3 A
Rating current 65°C according to IEC 60947-2:74,4 A
Rating current 70°C according to IEC 60947-2:72,4 A
Power loss per pole at In:10,7 W
Power loss per pole at 0.63*In:4,2 W
Power loss per pole at 0.8*In:6,6 W
Total power loss under IN:32,1 W
Total power loss at 0.63*In:12,5 W
Total power loss at 0.8*In:19,9 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:75 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
DIN rail mounting with optional adaptator:no
Type of connection:with screw
Range of the magnetic adjustment:1000 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C