  • Company
  • Products
  • Solutions
  • Downloads & Services
  • Videos
  • Hager. A partner made for you.
    We are a family-business shaping tomorrow’s electrical world to make people’s lives on our planet safer, cleaner and more enjoyable.
  • Watch and subscribe

HDA160Z

HDA160Z MCCB h3 x160 TM 3x160A 18kA

HDA160Z

MCCB h3 x160 TM 3x160A 18kA

Cat ref.:HDA160Z
prt.
EAN No.:

3250613136147

P.U.:1 prt.
Technical Characteristics
Number of protected poles:3
Number of poles:3 P
Type of pole:3P3D
Trip Unit:TM F/F
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Rated insulation voltage:690 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:18 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:18 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:18 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:18 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:18 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:18 kA
Thermal protection nob setting xIN:1
Range of the thermal adjustment:160 A
Rating current 10°C according to IEC 60947-2:187,2 A
Rating current 150°C according to IEC 60947-2:184 A
Rating current 20°C according to IEC 60947-2:180,7 A
Rating current 25°C according to IEC 60947-2:177,4 A
Rating current 30°C according to IEC 60947-2:174,1 A
Rating current 35°C according to IEC 60947-2:170,7 A
Rating current 40°C according to IEC 60947-2:167,2 A
Rating current 45°C according to IEC 60947-2:163,6 A
Rating current 50°C according to IEC 60947-2:160 A
Rating current 55°C according to IEC 60947-2:156,2 A
Rating current 60°C according to IEC 60947-2:152,4 A
Rating current 65°C according to IEC 60947-2:148,5 A
Rating current 70°C according to IEC 60947-2:144,4 A
Power loss per pole at In:14,6 W
Total power loss under IN:43,8 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:75 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Type of connection:with screw
Range of the magnetic adjustment:1600 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C
  • HDA160Z
    HDA160Z MCCB h3 x160 TM 3x160A 18kA
    HDA160Z
  • HDA160Z MCCB h3 x160 TM 3x160A 18kA
Customer who viewed this item also viewed
HNA100Z MCCB h3 x160 TM 3x100A 40kA
MCCB h3 x160 TM 3x100A 40kA
Data is subject to errors and technical modifications.