HHA039Z

No picture available

MCCB h3 x160 TM 2x40A 25kA

Cat ref.:HHA039Z
prt.
EAN No.:

3250613332372

P.U.:1 prt.
Technical Characteristics
Number of protected poles:2
Number of poles:2 P
Type of pole:2P2D
Trip Unit:TM F/F
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Rated insulation voltage:690 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:20 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Thermal protection nob setting xIN:1
Range of the thermal adjustment:40 A
Rating current 10°C according to IEC 60947-2:49,5 A
Rating current 150°C according to IEC 60947-2:48,4 A
Rating current 20°C according to IEC 60947-2:47,3 A
Rating current 25°C according to IEC 60947-2:46,1 A
Rating current 30°C according to IEC 60947-2:45 A
Rating current 35°C according to IEC 60947-2:43,8 A
Rating current 40°C according to IEC 60947-2:42,5 A
Rating current 45°C according to IEC 60947-2:41,3 A
Rating current 50°C according to IEC 60947-2:40 A
Rating current 55°C according to IEC 60947-2:38,6 A
Rating current 60°C according to IEC 60947-2:37,2 A
Rating current 65°C according to IEC 60947-2:35,7 A
Rating current 70°C according to IEC 60947-2:34,2 A
Power loss per pole at In:3,7 W
Total power loss under IN:7,3 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:50 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Type of connection:with screw
Range of the magnetic adjustment:600 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C