•  
  • Company
  • Products
  • Solutions
  • Downloads & Services
  • Videos
  • Hager. A partner made for you.
    We are a family-business shaping tomorrow’s electrical world to make people’s lives on our planet safer, cleaner and more enjoyable.
  • Watch and subscribe

HHA050Z

HHA050Z MCCB h3 x160 TM 3x50A 25kA

HHA050Z

MCCB h3 x160 TM 3x50A 25kA

Cat ref.:HHA050Z
prt.
EAN No.:

3250613136208

P.U.:1 prt.
Technical Characteristics
Number of protected poles:3
Number of poles:3 P
Type of pole:3P3D
Trip Unit:TM F/F
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Rated insulation voltage:690 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:20 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Thermal protection nob setting xIN:1
Range of the thermal adjustment:50 A
Rating current 10°C according to IEC 60947-2:60,4 A
Rating current 150°C according to IEC 60947-2:59,2 A
Rating current 20°C according to IEC 60947-2:58 A
Rating current 25°C according to IEC 60947-2:56,7 A
Rating current 30°C according to IEC 60947-2:55,4 A
Rating current 35°C according to IEC 60947-2:54,1 A
Rating current 40°C according to IEC 60947-2:52,8 A
Rating current 45°C according to IEC 60947-2:51,4 A
Rating current 50°C according to IEC 60947-2:50 A
Rating current 55°C according to IEC 60947-2:48,5 A
Rating current 60°C according to IEC 60947-2:47 A
Rating current 65°C according to IEC 60947-2:45,4 A
Rating current 70°C according to IEC 60947-2:43,8 A
Power loss per pole at In:5,8 W
Total power loss under IN:17,3 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:75 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Type of connection:with screw
Range of the magnetic adjustment:600 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C
  • HHA050Z
    HHA050Z MCCB h3 x160 TM 3x50A 25kA
    HHA050Z
  • HHA050Z MCCB h3 x160 TM 3x50A 25kA
Data is subject to errors and technical modifications.