HHA100Z

HHA100Z MCCB h3 x160 TM 3x100A 25kA

HHA100Z

MCCB h3 x160 TM 3x100A 25kA

Cat ref.:HHA100Z
prt.
EAN No.:

3250613136239

P.U.:1 prt.
Technical Characteristics
Number of protected poles:3
Number of poles:3 P
Type of pole:3P3D
Trip Unit:TM F/F
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Rated insulation voltage:690 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:25 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:20 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:20 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Thermal protection nob setting xIN:1
Range of the thermal adjustment:100 A
Rating current 10°C according to IEC 60947-2:120,5 A
Rating current 150°C according to IEC 60947-2:118,1 A
Rating current 20°C according to IEC 60947-2:115,7 A
Rating current 25°C according to IEC 60947-2:113,2 A
Rating current 30°C according to IEC 60947-2:110,7 A
Rating current 35°C according to IEC 60947-2:108,1 A
Rating current 40°C according to IEC 60947-2:105,5 A
Rating current 45°C according to IEC 60947-2:102,7 A
Rating current 50°C according to IEC 60947-2:100 A
Rating current 55°C according to IEC 60947-2:97,1 A
Rating current 60°C according to IEC 60947-2:94,1 A
Rating current 65°C according to IEC 60947-2:91,1 A
Rating current 70°C according to IEC 60947-2:87,9 A
Power loss per pole at In:13 W
Total power loss under IN:39 W
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Depth of installed product:68 mm
Height of installed product:130 mm
Width of installed product:75 mm
Critical distance switching emission/earthed part bottom:40 mm
Critical distance switching emission/earthed part left:50 mm
Critical distance switching emission/earthed part right:50 mm
Critical distance switching emission/earthed part top:40 mm
Critical distance switching emission/insulated plate:30 mm
Critical distance switching emission/live part:50 mm
Type of connection:with screw
Range of the magnetic adjustment:1500 A
Can be accessorized:yes
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Temperature of calibration:50 °C
  • HHA100Z
    HHA100Z MCCB h3 x160 TM 3x100A 25kA
    HHA100Z
  • HHA100Z MCCB h3 x160 TM 3x100A 25kA
Customer who viewed this item also viewed
HHA063Z MCCB X160 3P 25kA 63A
MCCB X160 3P 25kA 63A
MCCB h400 3P 50kA 400A TM
HHA160Z MCCB X160 3P 25kA 160A
MCCB X160 3P 25kA 160A
HHA125Z MCCB X160 3P 25kA 125A
MCCB X160 3P 25kA 125A
SBN390 3P 100A Switch
3P 100A Switch
SBN340 3P 40A Switch
3P 40A Switch
NCN320A MCB 3P 10kA C-20A 3M
MCB 3P 10kA C-20A 3M
NCN132A MCB 1P 10kA C-32A 1M
MCB 1P 10kA C-32A 1M
HHA040Z MCCB h3 x160 TM 3x40A 25kA
MCCB h3 x160 TM 3x40A 25kA
HHA018Z MCCB X160 1P 25kA 20A
MCCB X160 1P 25kA 20A
CD441J RCCB 4P 40A 30mA AC
RCCB 4P 40A 30mA AC
CD426J RCCB 4P 25A 30mA AC
RCCB 4P 25A 30mA AC
AD190 RCBO 1M 1P 10kA C-32A 30mA AC
RCBO 1M 1P 10kA C-32A 30mA AC
Data is subject to errors and technical modifications.