HHB100Z

HHB100Z MCCB X250 3P 25kA 100A TM

HHB100Z

MCCB X250 3P 25kA 100A TM

Cat ref.:HHB100Z
prt.
EAN No.:

3250613347536

P.U.:1 prt.
Technical Characteristics
Type of order:Toggle
Type of case:Fixed built-in
Number of poles:3 P
Type of pole:3P3D
Complete device with protection unit:yes
Trip Unit:TM F/F
Integrated earth fault protection:no
Compatible with DIN rail mounting:no
Motor drive integrated:no
Frequency:50/60 Hz
Rated operational voltage Ue:220/415 V
Rated insulation voltage:800 V
Rated impulse withstand voltage:8000 V
With under voltage release:no
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:25 kA
Rated service breaking capacity Ics AC according IEC 60947-2:80 %
Breaking capacity on 1 pole with 230 V NF 60947-2:21 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:9 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:35 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:25 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:15 kA
Rated ultimate short-circuit breaking capacity Icu under 690V AC IEC 60947-2:2 kA
Thermal protection nob setting xIN:1
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:1
Correction factor of rating current for 4 and 5 devices placed side-by-side:1
Correction factor of rating current for 6 devices placed side-by-side:1
Power loss per pole at In:5,9 W
Total power loss under IN:17,7 W
Tripmode:TM
Time of response when opening:10 ms
Electric endurance in number of cycles:1000
Number of mechanical operations:4000
Tightening torque:12Nm
DIN rail mounting with optional adaptator:yes
Connection cross-sect. rigid cable:35 / 185mm²
Connection cross-sect. flexible conductor:35 / 150mm²
Connection:Front connection
Type of connection:Terminal
Magnetic protection nob setting xIN:10
Setting type In or Ith:IN
Range of the magnetic adjustment:1300 A
Motor drive optional:yes
Category of use:A
Standard text:IEC 60947-2
European directive WEEE:concerned
Protection index IP:IP4X
Altitude:2000 m
Storage temperature:-35 to 70 °C
Air humidity protection:for all climates
  • HHB100Z
    HHB100Z MCCB X250 3P 25kA 100A TM
    HHB100Z
  • HHB100Z MCCB X250 3P 25kA 100A TM
Customer who viewed this item also viewed
HNA100Z MCCB h3 x160 TM 3x100A 40kA
MCCB h3 x160 TM 3x100A 40kA
HHB200Z MCCB X250 3P 25kA 200A TM
MCCB X250 3P 25kA 200A TM
HHA160Z MCCB X160 3P 25kA 160A
MCCB X160 3P 25kA 160A
HHA100Z MCCB h3 x160 TM 3x100A 25kA
MCCB h3 x160 TM 3x100A 25kA
MCCB x250 3P 40kA 200A TM
HHD400U MCCB h400 3P 25kA 400A TM
MCCB h400 3P 25kA 400A TM
HHB160Z MCCB X250 3P 25kA 160A TM
MCCB X250 3P 25kA 160A TM
HHA063Z MCCB X160 3P 25kA 63A
MCCB X160 3P 25kA 63A
Data is subject to errors and technical modifications.