h3 MCCB h250 3x250A Plug In 50kA HNC250G

EAN-Nr.
3250613123185
Packaging
1 Prt.

This product is now obsolete. However, this page remains available for information purposes.


Technical characteristics

Architecture
  • Number of poles
    3 P
Functions
  • Complete device with protection unit
    Yes
  • Trip Unit
    LSI
  • Integrated earth fault protection
    No
Main electrical features
  • Rated operational voltage Ue
    220 / 690 V
  • Frequency
    50/60 Hz
Voltage
  • Rated insulation voltage
    800 V
  • Rated impulse withstand voltage
    8 kV
  • With under voltage release
    No
Electric current
  • Rated current
    250 A
  • Breaking capacity on 1 pole for IT 400V NF 60947-2
    9 kA
  • Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
    85 kA
  • Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
    50 kA
  • Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
    50 kA
Current correction factors
  • Correction factor of rating current for 2 devices placed side-by-side
    1
  • Correction factor of rating current for 3 devices placed side-by-side
    1
  • Correction factor of rating current for 4 and 5 devices placed side-by-side
    1
  • Correction factor of rating current for 6 devices placed side-by-side
    1
Tripping
  • Tripmode
    LSI
  • Time of response when opening
    10 ms
Endurance
  • Electric endurance in number of cycles
    1000
  • Number of mechanical operations
    4000
Installation, mounting
  • DIN rail mounting with optional adaptator
    Yes
Connection
  • Connection cross-sect. flexible conductor
    35 / 150mm²
  • Type of connection
    Terminal
Settings
  • Range of the magnetic adjustment
    1400 / 1750 / 2240 / 2800 / 3150 / 3250 / 3250 A
Equipment
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as normally open contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Motor drive optional
    Yes
Standards
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP4X
Use conditions
  • Operating temperature
    -25…70 °C
  • Altitude
    2000 m
  • Air humidity protection
    for all climates
  • Storage/transport temperature
    -35…70 °C

Downloads

  • Product image

    Image HNC250G  | Hager

    Product Image HNC250G

  • Product notice

    Image Instruction manuals for HNC250G  | Hager

    Instruction manuals for HNC250G

    disjoncteur boîtier moulé 250A

    PDF
    930 KB
More documentation