Cat ref.: | ESC240S |
EAN No.: | 3250612400287 |
P.U.: | 4 prt. |
Type of order: | Not applicable |
Number of poles: | 2 P |
Frequency: | 50/60 Hz |
Rated operational voltage Ue: | 400 V |
Rated insulation voltage: | 440 V |
Command voltage AC: | 230 V |
Rated impulse withstand voltage: | 4 kV |
Acceptable current load with AC7 category A: | 40 A |
Acceptable current load with AC7 category B: | 25 A |
Thermal rated current outside of housings: | 40 A |
Inrush power absorbed: | 4,5 W |
Operating consumption: | 4,5 W |
Contact rating with 230 V in AC7 category A: | 7,3 kW |
Contact rating with 230 V in AC7 category B: | 2,6 kW |
Contact rating with 400 V in AC7 category A: | 22 kW |
Contact rating with 400 V in AC7 category B: | 7,8 kW |
Power loss per contact: | 3,2 W |
Total power loss under IN: | 10,9 W |
Power dissipation per coil: | 4,5 W |
Time of response when closing: | 25 ms |
Time of response when opening: | 20 ms |
Winding resistance: | 9200 Ω |
Electric endurance in number of cycles: | 30000 |
Number of mechanical operations: | 1000000 |
Depth of installed product: | 60 mm |
Height of installed product: | 85 mm |
Width of installed product: | 54 mm |
Max. load fluorescent lamp: | 1900 VA |
Max. power with fluorescent parallel lamps: | 1300 VA |
Fluorescent lamps in duo circuit: | 3000 VA |
Max. power with incandescent lamps: | 4000 W |
Tightening torque: | Coil: 2,5Nm, Power: 3,5Nm |
Max cable connect. cross section (flexible) for control: | 1 to 6 mm² |
Connection cross-section of the control cable solid: | 1 to 10 mm² |
Connection cross-sect. rigid cable: | 4 /25mm² |
Connection cross-sect. flexible conductor: | 4 / 16mm² |
Type of connection: | with screw |
Number of contacts: | 2 |
Type of contacts: | 2NO |
Can be accessorized: | yes |
Local operation/hand operation: | no |
European directive WEEE: | concerned |
Protection class: | isol.class II |
Protection index IP: | 2 |
Storage temperature: | -40 to 80 °C |
Device family: | ESC |