LS603
Fuse carrier 3P 50A L51 acc. 4.5M
Cat ref.: | LS603 |
EAN No.: | 3250614196034 |
P.U.: | 1 prt. |
Number of poles: | 3 P |
Type of pole: | 3 P |
Indicator lamp: | no |
Top connection alignement for modular devices: | Aligned terminal |
Frequency: | 50 Hz |
Rated operational voltage Ue: | 690 V |
Rating current of fuse cartridge: | 2/4/6/10/12/16/20/25/32/40/45/50 A |
Correction factor of the acceptable current of juxtaposition > 10 phases: | 0,7 |
Correction factor of acceptable current rating for 1-3 phase placed side-by-side: | 1 |
Correction coef of the acceptable current of juxtaposition from 4 to 6 phases: | 0,9 |
Correction factor of acceptable current rating for 7-9 phases placed side-by-sid: | 0,85 |
Correction coefficient of the acceptable current with 20°C: | 1 |
Correction factor of acceptable current rating with 30°C: | 0,95 |
Correction coefficient of the acceptable current up to 40°C: | 0,9 |
Correction coefficient of the acceptable current up to 50°C: | 0,8 |
CharactFuse: | gG |
Fuse Size: | 14 x 51 |
Power loss per pole at In: | 1,25 W |
Total power loss under IN: | 19 W |
Number of mechanical operations: | 5000 |
Depth of installed product: | 93 mm |
Height of installed product: | 107 mm |
Width of installed product: | 78,75 mm |
Tightening torque: | 3,6Nm |
Connection cross-sect. rigid cable: | 35mm² |
Connection cross-sect. flexible conductor: | 25mm² |
European directive WEEE: | concerned |
Protection index IP: | IP20 |
Degree of pollution according to IEC 60664 / IEC 60947-2: | 3 |
Storage temperature: | -25 to 80 °C |
Temperature of calibration: | 30 °C |
Data is subject to errors and technical modifications.