Fuse carrier 1P 125A 690V L58 accessoriability 2M LS701

EAN-Nr.
3250614197017
Packaging
1 Prt.

Technical characteristics

Architecture
  • Number of poles
    1 P
  • Type of pole
    1 P
  • Fixing mode
    DIN rail type O (symmetrical)
Functions
  • Concurrently switching N-neutral
    No
Configuration
  • Number of modules
    2
Controls and indicators
  • Indicator lamp
    no
Connectivity
  • Top connection alignement for modular devices
    Aligned terminal
Main electrical features
  • Rated operational voltage Ue
    690 V
  • Frequency
    50 Hz
Electric current
  • Rated current
    125 A
  • Rating current of fuse cartridge
    20 / 25 / 32 / 40 / 50 / 63 / 80 / 100 / 125 A
Current correction factors
  • Correction factor of the acceptable current of juxtaposition > 10 phases
    0.7
  • Correction factor of acceptable current rating for 1-3 phase placed side-by-side
    1
  • Correction coef of the acceptable current of juxtaposition from 4 to 6 phases
    0.9
  • Correction factor of acceptable current rating for 7-9 phases placed side-by-sid
    0.85
  • Correction coefficient of the acceptable current up to 40°C
    0.9
  • Correction coefficient of the acceptable current up to 50°C
    0.8
  • Correction coefficient of the acceptable current with 20°C
    1
  • Correction factor of acceptable current rating with 30°C
    0.95
Dimensions
  • Depth of installed product
    96 mm
  • Height of installed product
    125 mm
  • Width of installed product
    35 mm
Power
  • Total power loss under IN
    12.84 W
  • Power loss per pole at In
    2.94 W
Endurance
  • Number of mechanical operations
    5000
Cover, door
  • Interlockable
    Yes
Connection
  • Connection cross-sect. flexible conductor
    35 mm² max.
  • Connection cross-sect. rigid cable
    50mm² max.
Standards
  • European directive WEEE
    concerned
Safety
  • Protection index IP
    IP20
Use conditions
  • Operating temperature
    -5…40 °C
  • Degree of pollution according to IEC 60664 / IEC 60947-2
    3
  • Storage/transport temperature
    -25…80 °C
temperatur
  • Temperature of calibration
    30 °C

Downloads

  • Product image

    Image LS701  | Hager

    Product Image LS701

  • Product declaration

    Image EU Declaration of conformity for LS701  | Hager

    EU Declaration of conformity for LS701

    Declaration

    PDF
    126 KB