HLF180S

HLF180S MCB 1P 10kA C-80A 1.5M

HLF180S

MCB 1P 10kA C-80A 1.5M

Cat ref.:HLF180S
prt.
EAN No.:

3250613230852

P.U.:1 prt.
Technical Characteristics
Number of protected poles:1
Number of poles:1 P
Type of pole:1 P
Curve:C
Rated short circuit breaking capacity Icn AC according IEC60898-1:10 kA
Rated operational voltage Ue:240/415 V
Frequency:50/60 Hz
Type of supply voltage:AC
Rated insulation voltage:500 V
Rated impulse withstand voltage:6000 V
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:10 kA
Rated service breaking capacity Ics AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics AC according IEC 60947-2:75 %
Breaking capacity on 1 pole with 400 V NF 60947-2:4,5 kA
Breaking capacity on 1 pole with 415 V NF 60947-2:4,5 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:10 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:10 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:10 kA
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
Magnetic regulating currrent at 40° C:5/10 In
Rating current -15°C:109 A
Rating current -20°C:112 A
Rating current 0°C:99,2 A
Rating current 10°C:92,8 A
Rating current -10°C:106 A
Rating current 15°C:89,6 A
Rating current 20°C:86,4 A
Rating current 25°C:83,2 A
Rating current -25°C:115 A
Rating current 30°C:80 A
Rating current 35°C:77,6 A
Rating current 40°C:75,1 A
Rating current 45°C:72,6 A
Rating current 5°C:96 A
Rating current -5°C:102 A
Rating current 50°C:70 A
Rating current 55°C:67,2 A
Rating current 60°C:64,3 A
Rating current -10°C according to IEC 60947-2:112 A
Rating current -15°C according to IEC 60947-2:115 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Maximum power loss per pole according to the product standard:15 W
Total power loss under IN:6,18 W
Power loss per pole at In:6,18 W
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:90 mm
Width of installed product:27 mm
Tightening torque:3,5 to 5Nm
Connection cross-sect. flexible cable:35mm²
Connection cross-sect. rigid cable:70mm²
type of connection:terminal with tightening compensation system
Can be accessorized:yes
Standard text:EN 60898-1, IEC 60 947-2
European directive RoHs:voluntary compliance
European directive WEEE:concerned
Protection index IP:IP20
Degree of pollution according to IEC 60664 / IEC 60947-2:3
Altitude:2000 m
Storage temperature:-25 to 80 °C
Air humidity protection:for all climates