  • Company
  • Products
  • Solutions
  • Downloads & Services
  • Videos
  • Hager. A partner made for you.
    We are a family-business shaping tomorrow’s electrical world to make people’s lives on our planet safer, cleaner and more enjoyable.
  • Watch and subscribe

MC220A

MC220A MCB 2P 6kA C-20A 2M

MC220A

MCB 2P 6kA C-20A 2M

Cat ref.:MC220A
prt.
EAN No.:

3250614337345

P.U.:6 prt.
Technical Characteristics
Number of protected poles:2
Number of poles:2 P
Type of pole:2 P
Curve:C
Bottom connection alignement for modular devices:Aligned terminal
Top connection alignement for modular devices:Aligned terminal
Frequency:50/60 Hz
Rated short circuit breaking capacity Icn AC according IEC60898-1:6 kA
Type of supply voltage:AC
Rated operational voltage Ue:230/400 V
Rated insulation voltage:500 V
Rated impulse withstand voltage:4000 V
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1:6 kA
Rated service breaking capacity Ics AC according IEC 60898-1:6 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:6 kA
Magnetic regulating currrent at 40° C:5/10 In
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
Rating current -15°C:26,74 A
Rating current -20°C:27,39 A
Rating current 0°C:24,81 A
Rating current 10°C:23,52 A
Rating current -10°C:26,41 A
Rating current 15°C:22,88 A
Rating current 20°C:22,23 A
Rating current 25°C:21,59 A
Rating current -25°C:28,03 A
Rating current 30°C:20 A
Rating current 35°C:20,3 A
Rating current 40°C:19,66 A
Rating current 45°C:19,01 A
Rating current 5°C:24,17 A
Rating current -5°C:25,45 A
Rating current 50°C:19 A
Rating current 55°C:17,73 A
Rating current 60°C:17,08 A
Rating current 65°C:16,44 A
Rating current 70°C:15,79 A
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Power loss per pole at In:2,18 W
Total power loss under IN:4,35 W
Electric endurance in number of cycles:10000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:35 mm
Type of top connection for modular devices:with screw
Tightening torque:2,8Nm
Type of Bottom Connection for modular devices:BIconnect
Connection cross-sect. rigid cable:1 / 35mm²
Connection cross-sect. flexible conductor:1 / 25mm²
Type of connection:with screw
Connection cross section of access and exit with screws, for flexible conductor:1/25 mm²
Connection cross-section of input and output with screws, for massive conductors:1/35 mm²
Standard text:EN 60898-1
European directive WEEE:concerned
Protection index IP:IP20
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Storage temperature:-25 to 80 °C
Air humidity protection:for all climates
  • MC220A
    MC220A MCB 2P 6kA C-20A 2M
    MC220A
  • MC220A MCB 2P 6kA C-20A 2M
Data is subject to errors and technical modifications.