  • Our Company
  • Products
  • Solutions
  • Downloads & Services

NC416A

No picture available

MCB 4P 10kA C-16A 4M

Cat ref.:NC416A
prt.
EAN No.:

3250614637735

P.U.:3 prt.
Technical Characteristics
Number of protected poles:4
Number of poles:4 P
Type of pole:4 P
Curve:C
Rated short circuit breaking capacity Icn AC according IEC60898-1:10 kA
Rated operational voltage Ue:230/400 V
Frequency:50/60 Hz
Type of supply voltage:AC
Rated insulation voltage:500 V
Rated impulse withstand voltage:4000 V
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1:10 kA
Rated service breaking capacity Ics AC according IEC 60898-1:7,5 kA
Breaking capacity on 1 pole with 400 V NF 60947-2:3 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:10 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:10 kA
Rated ultimate short-circuit breaking capacity Icu under 440V AC IEC 60947-2:10 kA
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
Magnetic regulating currrent at 40° C:5/10 In
min/maxi threshold value of the DC magnetic operation:7/15 In
min/maxi threshold value of the DC thermal operation:1,13/1,45 In
Rating current -15°C:19,8 A
Rating current -20°C:20,1 A
Rating current 0°C:18,6 A
Rating current 10°C:17,8 A
Rating current -10°C:19,4 A
Rating current 15°C:17,3 A
Rating current 20°C:16,9 A
Rating current 25°C:16,5 A
Rating current -25°C:20,5 A
Rating current 30°C:16 A
Rating current 35°C:15,5 A
Rating current 40°C:15 A
Rating current 45°C:14,5 A
Rating current 5°C:18,2 A
Rating current -5°C:19 A
Rating current 50°C:14 A
Rating current 55°C:13,5 A
Rating current 60°C:12,9 A
Rating current 65°C:12,4 A
Rating current 70°C:11,9 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1
Maximum power loss per pole according to the product standard:3,5 W
Total power loss under IN:10,7 W
Power loss per pole at In:2,81 W
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:70 mm
Tightening torque:2,8Nm
type of connection:with screw
Top and bottom screw terminals connection capacity with rigid cable:1/25 mm²
Top and bottom screw terminals connection capacity with flexible cable:1/16 mm²
Can be accessorized:yes
Standard text:EN 60898-1
European directive WEEE:concerned
Protection index IP:IP20
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Storage temperature:-25 to 80 °C
Air humidity protection:for all climates
  • NC416A
    No picture available
Data is subject to errors and technical modifications.