  • Our Company
  • Products
  • Solutions
  • Downloads & Services

NCN132A

NCN132A MCB 1P 10kA C-32A 1M

NCN132A
NCN132A MCB 1P 10kA C-32A 1M
NCN132A MCB 1P 10kA C-32A 1M

MCB 1P 10kA C-32A 1M

Cat ref.:NCN132A
prt.
EAN No.:

3250614615559

P.U.:12 prt.
Technical Characteristics
Neutral position:without neutral
Number of protected poles:1
Number of poles:1 P
Type of pole:1 P
Concurrently switching N-neutral:no
Curve:C
Bottom connection alignement for modular devices:Aligned terminal
Top connection alignement for modular devices:Aligned terminal
Type of supply voltage:AC
Rated operational voltage Ue:240/415 V
Minimum threshold voltage (Ue min):12 V
Rated insulation voltage:500 V
Max operating voltage:440 V
Rated impulse withstand voltage:6000 V
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:10 kA
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1:10 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 220V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 230V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 240V AC according IEC 60898-1:7,5 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2:15 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:15 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:15 kA
Magnetic regulating currrent at 40° C:5/10 In
min/maxi threshold value of the DC magnetic operation:7/15 In
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
min/maxi threshold value of the DC thermal operation:1,13/1,45 In
Rating current 0°C according to IEC 60947-2:40,33 A
Rating current 10°C according to IEC 60947-2:38,81 A
Rating current -10°C according to IEC 60947-2:41,8 A
Rating current 150°C according to IEC 60947-2:38,02 A
Rating current -15°C according to IEC 60947-2:42,51 A
Rating current 20°C according to IEC 60947-2:37,22 A
Rating current -20°C according to IEC 60947-2:43,21 A
Rating current 25°C according to IEC 60947-2:36,4 A
Rating current -25°C according to IEC 60947-2:43,9 A
Rating current 30°C according to IEC 60947-2:35,57 A
Rating current 35°C according to IEC 60947-2:34,71 A
Rating current 40°C according to IEC 60947-2:33,83 A
Rating current 45°C according to IEC 60947-2:32,93 A
Rating current 5°C according to IEC 60947-2:39,57 A
Rating current -5°C according to IEC 60947-2:41,07 A
Rating current 50°C according to IEC 60947-2:32 A
Rating current 55°C according to IEC 60947-2:31,04 A
Rating current 60°C according to IEC 60947-2:30,06 A
Rating current 65°C according to IEC 60947-2:29,04 A
Rating current 70°C according to IEC 60947-2:27,98 A
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1,1
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Power loss per pole at In:3,65 W
Maximum power loss per pole according to the product standard:6 W
Total power loss under IN:3,65 W
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:17,5 mm
Type of top connection for modular devices:with screw
Tightening torque:2,8Nm
Type of bottom rail clip for modular devices:plastic
Type of top rail clip for modular devices:NA
Type of Bottom Connection for modular devices:BIconnect
Bottom removability for modular devices:yes
Top removability for modular devices:yes
Suitable for flush-mounting:yes
Upstream cage clamp delivery status:opened
Downstream cage clamp delivery status:opened
Downstream screw terminal connection capacity with flexible conductor:1/25 mm²
Upstream screw terminals connection capacity with flexible cable:1/25 mm²
Down. screw term. capacity rigid cable:1/35 mm²
Rigid cable screw up connector cross section:1/35 mm²
Can be accessorized:yes
Standard text:EN 60898-1, AS/NZ 60898-1
European directive RoHs:voluntary compliance
European directive WEEE:concerned
Protection index IP:IP20
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Storage temperature:-25 to 80 °C
Temperature of calibration:30 °C
  • NCN132A
    NCN132A MCB 1P 10kA C-32A 1M
    NCN132A
  • NCN132A
    NCN132A MCB 1P 10kA C-32A 1M
    NCN132A
  • NCN132A MCB 1P 10kA C-32A 1M
  • NCN132A MCB 1P 10kA C-32A 1M
Data is subject to errors and technical modifications.