NDN425A

NDN425A MCB 4P 10kA D-25A 4M

Similar image
(Picture shows NDN440A)
NDN425A MCB 4P 10kA D-25A 4M
NDN425A MCB 4P 10kA D-25A 4M

MCB 4P 10kA D-25A 4M

Cat ref.:NDN425A
prt.
EAN No.:

3250614619410

P.U.:3 prt.
Technical Characteristics
Neutral position:without neutral
Number of protected poles:4
Number of poles:4 P
Type of pole:4 P
Curve:D
Bottom connection alignement for modular devices:Aligned terminal
Top connection alignement for modular devices:Aligned terminal
Type of supply voltage:AC
Rated operational voltage Ue:415 V
Minimum threshold voltage (Ue min):12 V
Rated insulation voltage:500 V
Max operating voltage:440 V
Rated impulse withstand voltage:6000 V
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:15 kA
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:10 kA
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1:10 kA
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1:10 kA
Rated short circuit breaking capacity Icn under 380V AC according IEC 60898-1:10 kA
Rated short circuit breaking capacity Icn under 415V AC according IEC 60898-1:10 kA
Rated service breaking capacity Ics AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 220V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 230V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 240V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 380V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 400V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 415V AC according IEC 60898-1:7,5 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:15 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:15 kA
Magnetic regulating currrent at 40° C:10/14,4 In
min/maxi threshold value of the DC magnetic operation:15/30 In
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
min/maxi threshold value of the DC thermal operation:1,13/1,45 In
Rating current -15°C:30,03 A
Rating current -20°C:30,54 A
Rating current 0°C:28,45 A
Rating current 10°C:27,35 A
Rating current -10°C:29,51 A
Rating current 25°C:25,61 A
Rating current -25°C:31,04 A
Rating current 30°C:25 A
Rating current 35°C:24,23 A
Rating current 40°C:23,44 A
Rating current 45°C:22,61 A
Rating current 5°C:27,91 A
Rating current -5°C:28,99 A
Rating current 50°C:21,76 A
Rating current 55°C:20,87 A
Rating current 60°C:19,94 A
Rating current 65°C:18,97 A
Rating current 70°C:17,94 A
Rating current 0°C according to IEC 60947-2:31,75 A
Rating current 10°C according to IEC 60947-2:30,52 A
Rating current -10°C according to IEC 60947-2:32,93 A
Rating current 150°C according to IEC 60947-2:29,88 A
Rating current -15°C according to IEC 60947-2:33,51 A
Rating current 20°C according to IEC 60947-2:29,23 A
Rating current -20°C according to IEC 60947-2:34,07 A
Rating current 25°C according to IEC 60947-2:28,57 A
Rating current -25°C according to IEC 60947-2:34,63 A
Rating current 30°C according to IEC 60947-2:27,89 A
Rating current 35°C according to IEC 60947-2:27,2 A
Rating current 40°C according to IEC 60947-2:26,49 A
Rating current 45°C according to IEC 60947-2:25,75 A
Rating current 5°C according to IEC 60947-2:31,14 A
Rating current -5°C according to IEC 60947-2:32,34 A
Rating current 50°C according to IEC 60947-2:25 A
Rating current 55°C according to IEC 60947-2:23,98 A
Rating current 60°C according to IEC 60947-2:22,91 A
Rating current 65°C according to IEC 60947-2:21,79 A
Rating current 70°C according to IEC 60947-2:20,61 A
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1,1
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Power loss per pole at In:3,75 W
Maximum power loss per pole according to the product standard:4,5 W
Total power loss under IN:14,75 W
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:70 mm
Type of top connection for modular devices:with screw
Tightening torque:2,8Nm
Type of bottom rail clip for modular devices:plastic
Type of top rail clip for modular devices:NA
Type of Bottom Connection for modular devices:BIconnect
Bottom removability for modular devices:yes
Top removability for modular devices:yes
Suitable for flush-mounting:yes
Upstream cage clamp delivery status:opened
Downstream cage clamp delivery status:opened
Connection cross-section at output with screw, for flexible conductor:1/25 mm²
Connection cross-section of the access with screws, with flexible conductor:1/25 mm²
Connection cross-section at output with screw, for massive conductor:1/35 mm²
Connection cross-section for rigid conductor, upstream terminals with screws:1/35 mm²
Can be accessorized:yes
Standard text:EN 60898-1, AS/NZS 60898-1
European directive WEEE:concerned
Protection index IP:IP20
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Altitude:2000 m
Storage temperature:-25 to 80 °C
Temperature of calibration:30 °C
  • NDN425A
    NDN425A MCB 4P 10kA D-25A 4M
    Similar image
    (Picture shows NDN440A)
  • NDN425A
    NDN425A MCB 4P 10kA D-25A 4M
    NDN425A
  • NDN425A MCB 4P 10kA D-25A 4M
  • NDN425A MCB 4P 10kA D-25A 4M
Customer who viewed this item also viewed
85341131 HBNet WÄCH STANDARD 1,1m R.1 SCHWARZ GLÄ
HBNet WÄCH STANDARD 1, 1m R.1 SCHWARZ GLÄ
Data is subject to errors and technical modifications.