  • Our Company
  • Products
  • Solutions
  • Downloads & Services

NRN206

NRN206 MCB 2P 25kA C-6A 2M

NRN206

MCB 2P 25kA C-6A 2M

Cat ref.:NRN206
prt.
EAN No.:

3250614644986

P.U.:1 prt.
Technical Characteristics
Neutral position:without neutral
Number of protected poles:2
Number of poles:2 P
Type of pole:2 P
Fixing mode:Din-Rail
Curve:C
With fault indicator:no
Rated operational voltage Ue:415 V
Frequency:50/60 Hz
Type of supply voltage:AC
Rated insulation voltage:500 V
Minimum threshold voltage (Ue min):12 V
Rated impulse withstand voltage:6000 V
Breaking capacity on 1 pole with 400 V NF 60947-2:3 kA
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
Magnetic regulating currrent at 40° C:5/10 In
min/maxi threshold value of the DC magnetic operation:5/15 In
min/maxi threshold value of the DC thermal operation:1,13/1,45 In
Rating current -15°C:7,26 A
Rating current -20°C:7,39 A
Rating current 0°C:6,87 A
Rating current 10°C:6,59 A
Rating current -10°C:7,13 A
Rating current 15°C:6,45 A
Rating current 20°C:6,3 A
Rating current 25°C:6,15 A
Rating current -25°C:7,51 A
Rating current 30°C:6 A
Rating current 35°C:5,84 A
Rating current 40°C:5,68 A
Rating current 45°C:5,52 A
Rating current 5°C:6,73 A
Rating current -5°C:7 A
Rating current 50°C:5,35 A
Rating current 55°C:5,17 A
Rating current 60°C:4,99 A
Rating current 65°C:4,8 A
Rating current 70°C:4,6 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1
Maximum power loss per pole according to the product standard:3 W
Total power loss under IN:2,68 W
Power loss per pole at In:1,34 W
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:35 mm
Tightening torque:2,8Nm
Downstream screw terminal connection capacity with flexible conductor:1/25 mm²
Down. screw term. capacity rigid cable:1/35 mm²
Rigid cable screw up connector cross section:1/35 mm²
Upstream screw terminals connection capacity with flexible cable:1/25 mm²
type of connection:with screw
Top and bottom screw terminals connection capacity with rigid cable:1/35 mm²
Top and bottom screw terminals connection capacity with flexible cable:1/25 mm²
Can be accessorized:yes
Standard text:IEC 60 947-2
European directive RoHs:voluntary compliance
European directive WEEE:concerned
Protection index IP:IP20
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Storage temperature:-25 to 80 °C
Air humidity protection:for all climates
  • NRN206
    NRN206 MCB 2P 25kA C-6A 2M
    NRN206
  • NRN206 MCB 2P 25kA C-6A 2M
Data is subject to errors and technical modifications.