AD188
RCBO 1M 1P 10kA C-20A 30mA AC
Cat ref.: | AD188 |
EAN No.: | 3250611043157 |
P.U.: | 1 prt. |
Neutral position: | right |
Number of protected poles: | 1 |
Number of poles: | 1 P |
Type of pole: | 1 P |
Concurrently switching N-neutral: | no |
Curve: | C |
Frequency: | 50/60 Hz |
Rated short circuit breaking capacity Icn AC according IEC60898-1: | 10 kA |
Rated operational voltage Ue: | 230/240 V |
Rated insulation voltage: | 250 V |
Max operating voltage: | 253 V |
Rated impulse withstand voltage: | 4000 V |
Rated residual operating current: | 30 mA |
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1: | 10 kA |
Breaking and opening capacity: | 6 kA |
Magnetic regulating currrent at 40° C: | 5/10 In |
min/maxi threshold value of the AC thermal operation: | 1,13/1,45 In |
Rating current -15°C: | 24,73 A |
Rating current -20°C: | 25,25 A |
Rating current 0°C: | 23,15 A |
Rating current 10°C: | 22,1 A |
Rating current -10°C: | 24,2 A |
Rating current 15°C: | 21,58 A |
Rating current 20°C: | 21,05 A |
Rating current 25°C: | 20,53 A |
Rating current -25°C: | 25,78 A |
Rating current 30°C: | 20 A |
Rating current 35°C: | 19,6 A |
Rating current 40°C: | 19,2 A |
Rating current 45°C: | 18,8 A |
Rating current 5°C: | 22,63 A |
Rating current -5°C: | 23,68 A |
Rating current 50°C: | 18,4 A |
Rating current 55°C: | 18 A |
Rating current 60°C: | 17,6 A |
Correction factor of rating current for 2 devices placed side-by-side: | 1 |
Correction factor of rating current for 3 devices placed side-by-side: | 0,95 |
Correction factor of rating current for 4 and 5 devices placed side-by-side: | 0,9 |
Correction factor of rating current for 6 devices placed side-by-side: | 0,85 |
Power loss per pole at In: | 2,98 W |
Total power loss under IN: | 5,76 W |
Electric endurance in number of cycles: | 2000 |
Number of mechanical operations: | 1000 |
Depth of installed product: | 70 mm |
Height of installed product: | 115 mm |
Width of installed product: | 17,5 mm |
Tightening torque: | 2,1Nm |
Standard text: | IEC 61009-1, EN 61009-1 |
Protection index IP: | IP20 |
Residual current type: | AC |
Degree of pollution according to IEC 60664 / IEC 60947-2: | 2 |
Class of energy limitation I²t: | 3 |
Altitude: | 2000 m |
Storage temperature: | -25 to 60 °C |
Air humidity protection: | Execution II |
Data is subject to errors and technical modifications.