  • Our Company
  • Products
  • Solutions
  • Downloads & Services

AE116Z

AE116Z RCBO 1P 6kA C-16A 100mA type AC

AE116Z

RCBO 1P 6kA C-16A 100mA type AC

Cat ref.:AE116Z
prt.
EAN No.:

3250611050087

P.U.:1 prt.
Technical Characteristics
Neutral position:right
Number of protected poles:1
Number of poles:1 P
Type of pole:1 P
Curve:C
Rated short circuit breaking capacity Icn AC according IEC60898-1:6 kA
Rated operational voltage Ue:230/240 V
Frequency:50/60 Hz
Rated insulation voltage:250 V
Max operating voltage:253 V
Rated impulse withstand voltage:4000 V
Rated residual operating current:100 mA
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:6 kA
Breaking and opening capacity:6 kA
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
Magnetic regulating currrent at 40° C:5/10 In
Rating current -15°C:21,23 A
Rating current -20°C:21,74 A
Rating current 0°C:19,64 A
Rating current 10°C:18,51 A
Rating current -10°C:20,72 A
Rating current 15°C:17,91 A
Rating current 20°C:17,3 A
Rating current 25°C:16,66 A
Rating current -25°C:22,23 A
Rating current 30°C:16 A
Rating current 35°C:15,38 A
Rating current 40°C:14,75 A
Rating current 45°C:14,13 A
Rating current 5°C:19,08 A
Rating current -5°C:20,19 A
Rating current 50°C:13,5 A
Rating current 55°C:12,88 A
Rating current 60°C:12,25 A
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Total power loss under IN:4,74 W
Power loss per pole at In:2,88 W
Electric endurance in number of cycles:2000
Number of mechanical operations:1000
Depth of installed product:70 mm
Height of installed product:115 mm
Width of installed product:17,5 mm
Tightening torque:2,1Nm
Standard text:IEC 61009-1, EN 61009-1
Protection index IP:IP20
Residual current type:AC
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Class of energy limitation I²t:3
Altitude:2000 m
Storage temperature:-25 to 60 °C
Air humidity protection:Execution II