RCCB 2P 25A 100mA AC

Cat ref.:CE226J
EAN No.:


P.U.:1 prt.
Technical Characteristics
Number of poles:2 P
Rated residual operating current:100 mA
Residual current type:AC
Frequency:50 Hz
Rated operational voltage Ue:230 V
Neutral position:right
Altitude:2000 m
Can be accessorized:yes
Construction size (DIN 43880):1
Tightening torque:2,8Nm
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Short-time delayed tripping:no
Height of installed product:83 mm
Breaking and opening capacity:1,5 kA
Rating current -10°C:25 A
Rating current -15°C:25 A
Rating current -20°C:25 A
Rating current -25°C:25 A
Rating current -5°C:25 A
Rating current 0°C:25 A
Rating current 10°C:25 A
Rating current 15°C:25 A
Rating current 20°C:25 A
Rating current 25°C:25 A
Rating current 30°C:25 A
Rating current 35°C:25 A
Rating current 40°C:25 A
Rating current 45°C:25 A
Rating current 5°C:25 A
Rating current 50°C:25 A
Rating current 55°C:25 A
Rating current 60°C:25 A
Rating current 65°C:25 A
Rating current 70°C:21 A
Rated conditional short-circuit current Inc according to EN 61008-1:6 kA
Protection index IP:IP20
Width of installed product:35 mm
Fixing mode:Din-Rail
Electric endurance in number of cycles:2000
Number of mechanical operations:4000
Surge current strength (waves 8/20µs):0,25 kA
Depth of installed product:70 mm
Power loss per pole at In:0,7 W
Total power loss under IN:1,3 W
Connection cross-sect. rigid cable:25mm²
Connection cross-sect. flexible cable:16mm²
Storage temperature:-55 to 70 °C
European directive RoHs:voluntary compliance
European directive WEEE:concerned
Standard text:IEC 61008-1 ; EN 61008-1
type of connection:with screw
Rated insulation voltage:500 V
Rated impulse withstand voltage:4 kV