NDN316A

NDN316A MCB 3P 10kA D-16A 3M

NDN316A

MCB 3P 10kA D-16A 3M

Cat ref.:NDN316A
EAN No.:

3250614619243

This product is now obsolete. However, this page remains available for information purposes. Please contact your wholesaler in order to find appropriate replacement products. Obsolete reference: NDN316A Replacement reference:
Technical Characteristics
Neutral position:without neutral
Number of protected poles:3
Number of poles:3 P
Type of pole:3 P
Curve:D
Bottom connection alignement for modular devices:Aligned terminal
Top connection alignement for modular devices:Aligned terminal
Type of supply voltage:AC
Rated operational voltage Ue:415 V
Minimum threshold voltage (Ue min):12 V
Rated insulation voltage:500 V
Max operating voltage:440 V
Rated impulse withstand voltage:6000 V
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2:15 kA
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1:10 kA
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1:10 kA
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1:10 kA
Rated short circuit breaking capacity Icn under 380V AC according IEC 60898-1:10 kA
Rated short circuit breaking capacity Icn under 415V AC according IEC 60898-1:10 kA
Rated service breaking capacity Ics AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 220V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 230V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 240V AC according IEC 60947-2:15 kA
Rated service breaking capacity Ics under 380V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 400V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 415V AC according IEC 60947-2:7,5 kA
Rated service breaking capacity Ics under 220V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 230V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 240V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 380V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 400V AC according IEC 60898-1:7,5 kA
Rated service breaking capacity Ics under 415V AC according IEC 60898-1:7,5 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2:30 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2:15 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2:15 kA
Magnetic regulating currrent at 40° C:10/14,4 In
min/maxi threshold value of the DC magnetic operation:15/30 In
min/maxi threshold value of the AC thermal operation:1,13/1,45 In
min/maxi threshold value of the DC thermal operation:1,13/1,45 In
Rating current -15°C:19,56 A
Rating current -20°C:19,92 A
Rating current 0°C:18,45 A
Rating current 10°C:17,67 A
Rating current -10°C:19,2 A
Rating current 25°C:16,43 A
Rating current -25°C:20,27 A
Rating current 30°C:16 A
Rating current 35°C:15,48 A
Rating current 40°C:14,94 A
Rating current 45°C:14,38 A
Rating current 5°C:18,07 A
Rating current -5°C:18,83 A
Rating current 50°C:13,8 A
Rating current 55°C:13,19 A
Rating current 60°C:12,56 A
Rating current 65°C:11,89 A
Rating current 70°C:11,18 A
Rating current 0°C according to IEC 60947-2:20,89 A
Rating current 10°C according to IEC 60947-2:20,01 A
Rating current -10°C according to IEC 60947-2:21,74 A
Rating current 150°C according to IEC 60947-2:19,55 A
Rating current -15°C according to IEC 60947-2:22,15 A
Rating current 20°C according to IEC 60947-2:19,09 A
Rating current -20°C according to IEC 60947-2:22,55 A
Rating current 25°C according to IEC 60947-2:18,61 A
Rating current -25°C according to IEC 60947-2:22,95 A
Rating current 30°C according to IEC 60947-2:18,12 A
Rating current 35°C according to IEC 60947-2:17,61 A
Rating current 40°C according to IEC 60947-2:17,09 A
Rating current 45°C according to IEC 60947-2:16,55 A
Rating current 5°C according to IEC 60947-2:20,46 A
Rating current -5°C according to IEC 60947-2:21,32 A
Rating current 50°C according to IEC 60947-2:16 A
Rating current 55°C according to IEC 60947-2:15,3 A
Rating current 60°C according to IEC 60947-2:14,56 A
Rating current 65°C according to IEC 60947-2:13,78 A
Rating current 70°C according to IEC 60947-2:12,96 A
Correction factor of magnetic tripping with 100 Hz:1,1
Correction factor of magnetic tripping with 200 Hz:1,2
Correction factor of magnetic tripping with 400 Hz:1,5
Correction factor of magnetic tripping with 60 Hz:1,1
Correction factor of rating current for 2 devices placed side-by-side:1
Correction factor of rating current for 3 devices placed side-by-side:0,95
Correction factor of rating current for 4 and 5 devices placed side-by-side:0,9
Correction factor of rating current for 6 devices placed side-by-side:0,85
Power loss per pole at In:2,8 W
Maximum power loss per pole according to the product standard:3,5 W
Total power loss under IN:8,27 W
Electric endurance in number of cycles:4000
Number of mechanical operations:20000
Depth of installed product:70 mm
Height of installed product:83 mm
Width of installed product:52,5 mm
Type of top connection for modular devices:with screw
Tightening torque:2,8Nm
Type of bottom rail clip for modular devices:plastic
Type of top rail clip for modular devices:NA
Type of Bottom Connection for modular devices:BIconnect
Bottom removability for modular devices:yes
Top removability for modular devices:yes
Suitable for flush-mounting:yes
Upstream cage clamp delivery status:opened
Downstream cage clamp delivery status:opened
Connection cross-section at output with screw, for flexible conductor:1/25 mm²
Connection cross-section of the access with screws, with flexible conductor:1/25 mm²
Connection cross-section at output with screw, for massive conductor:1/35 mm²
Connection cross-section for rigid conductor, upstream terminals with screws:1/35 mm²
Can be accessorized:yes
Standard text:EN 60898-1, AS/NZS 60898-1
European directive WEEE:concerned
Protection index IP:IP20
Degree of pollution according to IEC 60664 / IEC 60947-2:2
Altitude:2000 m
Storage temperature:-25 to 80 °C
Temperature of calibration:30 °C